Case Study: Rosecrest Multi-Stage Furnace Install Riverton

Case Study: Rosecrest Multi-Stage Furnace Installation

Address area: Rosecrest master-planned community, western Riverton, UT 84065 (specific address confidential per homeowner request). Project completion: October 2025. Scope: Two-stage variable-speed condensing gas furnace installation replacing 2005 single-stage 80% AFUE original construction furnace. Home: 2,860 sq ft two-story with unfinished basement built 2005 in Rosecrest master-planned community, existing matched 2005 Carrier 13 SEER AC continuing in service. This case study documents the pre-installation evaluation identifying multi-stage upgrade opportunity, homeowner priorities favoring quiet operation and humidity control improvements, Carrier Performance series two-stage 96% AFUE furnace selection, coordination with existing matched AC, and homeowner outcome from the upgrade.

Project Background

Rosecrest Development Context

Rosecrest is a master-planned Riverton community developed primarily 1999–2015 covering western Riverton hillside areas. Housing stock features tract single-family residential typically 2,200–3,500 sq ft with typical 2000s master-planned envelope specifications (R-30 attic, R-13 walls, standard double-pane windows). Original HVAC installations from the era typically featured 80% AFUE atmospheric furnaces paired with 12–13 SEER AC on standard forced-air distribution.

Existing Equipment

2005 original construction HVAC:

  • Furnace: Carrier Comfort series 58STA 80% AFUE atmospheric single-stage gas furnace, 100,000 BTU/hr input capacity (oversized per typical 2005 rule-of-thumb sizing), PSC blower motor, standard programmable thermostat, atmospheric induced-draft venting through existing masonry chimney with metal B-vent liner
  • Air conditioner: Matched Carrier 24ABB6 13 SEER 3.5 ton AC (2005 original), R-410A refrigerant system, continuing in service

Pre-Installation Evaluation

Pre-installation evaluation identified upgrade opportunity: (1) 20 year-old furnace approaching end-of-service-life, homeowner ready for proactive replacement before failure scenario; (2) 80% AFUE atmospheric technology 15% less efficient than modern 95%+ AFUE condensing options; (3) single-stage cycling operation producing temperature swings and inconsistent humidity, homeowner particularly noting summer humidity control issues; (4) 100,000 BTU/hr input capacity oversized relative to actual 2,860 sq ft Manual J load, contributing to short-cycling and comfort issues; and (5) matched 2005 AC continuing in acceptable condition with likely 5–10 year remaining service life, warranting furnace-only replacement scope with future AC replacement scheduled separately.

Homeowner Priorities

Homeowner priorities established during pre-installation consultation: quieter operation (primary bedroom directly above mechanical room, existing single-stage furnace producing noticeable startup and cycling noise), improved humidity control (summer humidity levels 55–65% RH causing discomfort even at reasonable temperature setpoints), better temperature consistency (existing single-stage cycling producing 3–4°F swings around setpoint), energy efficiency improvement (Dominion Energy gas billing motivation), and reasonable equipment tier decision balancing feature benefits with cost.

Two-Stage Multi-Stage Selection Rationale

Two-Stage vs Variable-Speed Modulating

Equipment tier decision between two-stage 96% AFUE Carrier Performance series and premium variable-speed modulating 98% AFUE Carrier Infinity series:

  • Two-stage 96% AFUE Carrier Performance: Low-fire and high-fire operation (65% and 100% output capacity), ECM variable-speed blower, standard non-communicating thermostat compatible, 96% AFUE efficiency, cost approximately $6,400–$8,800 installed
  • Variable-speed 98% AFUE Carrier Infinity: 65% to 100% modulating operation, ECM variable-speed blower, communicating thermostat required, 98% AFUE efficiency (equipment rated, altitude-corrected similar to Performance series 96% AFUE), cost approximately $8,800–$11,400 installed

Two-Stage Selection Justification

Two-stage Performance series selected based on: (1) 65% low-fire operation provides much of the comfort benefit of full modulation (temperature swing reduction, longer run times for better humidity control, quieter operation than single-stage) at meaningfully lower cost, (2) ECM variable-speed blower provides continuous fan operation option and modulated blower speed matching stage operation, (3) 96% AFUE altitude-corrected efficiency essentially equivalent to Infinity 98% AFUE altitude-corrected efficiency in Bluffdale/Riverton climate, (4) standard non-communicating thermostat compatibility allows homeowner flexibility in thermostat selection (Nest, Ecobee, or Carrier smart thermostats), and (5) cost savings of approximately $2,400 versus premium tier applied to potential future matched AC replacement.

Manual J Load Calculation

Manual J load calculation for 2,860 sq ft home:

  • Total heating load: 54,800 BTU/hr at 9°F design temperature (Bluffdale/Riverton ASHRAE 99% winter)
  • Furnace sizing: 80,000 BTU/hr input capacity selected (76,800 BTU/hr output at 96% AFUE, altitude-corrected to ~68,400 BTU/hr effective output). Right-sizing eliminates prior 100,000 BTU/hr oversizing which contributed to short-cycling issues on existing equipment.
  • Cooling load coordination: Existing 3.5 ton AC matched properly with new furnace blower CFM capacity, cooling load analysis retained from prior installation

Equipment Selection

Carrier Performance Two-Stage 96% AFUE Furnace

Carrier Performance series 59TN6 two-stage 96% AFUE condensing gas furnace:

  • Model: 59TN6B080V17 (80,000 BTU/hr input matching Manual J calculation)
  • Efficiency: 96% AFUE (altitude-corrected ~85.4% seasonal efficiency at Bluffdale elevation)
  • Operation: Two-stage gas valve (65% low-fire / 100% high-fire), thermostat initiates low-fire operation with automatic escalation to high-fire if low-fire insufficient after specified timeout
  • Blower: ECM variable-speed blower motor with programmable speed profiles for heating, cooling, continuous fan, and dehumidification modes
  • Venting: PVC direct-vent installation with concentric side-wall termination
  • Warranty: 20-year heat exchanger warranty, 10-year parts warranty

Ecobee SmartThermostat

Ecobee SmartThermostat Premium selected as replacement thermostat: standard 24V non-communicating installation compatible with Carrier Performance series two-stage furnace, dual-stage heating control (initiates low-fire, escalates to high-fire per programmed timeout), Wi-Fi connectivity with Ecobee app for remote access and scheduling, room sensor integration for whole-home temperature averaging (Ecobee sensors placed in primary bedroom and living room), and Alexa/Google Home integration for voice control.

Installation Execution

Timeline

Total installation timeline: 2 days of active work. Day 1: existing furnace removal after gas shutoff and electrical disconnection, evaporator coil careful preservation (continues in service with existing matched AC), and new Carrier Performance 59TN6 furnace setting in mechanical room. Day 2: PVC direct-vent installation with side-wall penetration and concentric termination, chimney abandonment coordination, gas line connection with new shutoff valve and union, electrical connections to blower motor and controls, condensate line routing to floor drain, Ecobee thermostat installation and configuration with room sensors, and commissioning verification.

Chimney Abandonment

Existing masonry chimney abandoned for boiler-only venting: metal B-vent liner removed from chimney interior, chimney cap installed at chimney top preventing water infiltration, chimney flue closed at top and bottom preventing air infiltration, and existing chimney structure remains for aesthetic reasons but no longer functional for combustion venting. Gas water heater retained on separate metal B-vent through side wall (installed in 2019 water heater replacement scenario, not affected by furnace conversion).

Commissioning Verification

Combustion Analysis

Combustion analyzer verification with Bacharach InsightPlus at both low-fire and high-fire operation:

  • High-fire operation: CO 46 ppm, stack 195°F, O2 7.4%, efficiency 95.1%
  • Low-fire operation: CO 32 ppm, stack 165°F, O2 7.8%, efficiency 94.8%
  • Gas manifold pressure: 3.5" WC high-fire, 2.3" WC low-fire verified (matching manufacturer specification)

Airflow and Static Pressure

Airflow and static pressure verification:

  • Total external static pressure: 0.42" WC (within Carrier 0.50" WC maximum specification)
  • Heating high-fire CFM: 1,240 CFM measured
  • Heating low-fire CFM: 820 CFM measured (matched with low-fire capacity for proper temperature rise)
  • Cooling CFM: 1,380 CFM measured (400 CFM/ton for 3.5 ton AC)
  • Temperature rise: Heating high-fire 48°F, heating low-fire 42°F (both within Carrier specification 45–65°F range)

Ecobee Configuration Verification

Ecobee thermostat configuration verified: two-stage heating control with 15-minute timeout for low-fire before escalation to high-fire, humidity control mode enabled with Carrier furnace ECM blower coordination, room sensor averaging enabled with primary bedroom weighted higher during sleep hours, and scheduling programmed for household patterns.

Homeowner Outcome

Winter 2025–2026 Performance

Winter 2025–2026 heating season performance verification:

  • Temperature consistency: Two-stage operation reduced temperature swings from 3–4°F to 1–2°F around setpoint
  • Quiet operation: Low-fire operation approximately 40% quieter than prior single-stage (subjective homeowner assessment), primary bedroom no longer disturbed by furnace startup cycles
  • Cold snap performance: High-fire escalation properly engaged during cold snap conditions, home maintained at setpoint through 8°F outdoor low without difficulty

Anticipated Summer 2026 Performance

Anticipated summer 2026 humidity control improvement:

  • ECM blower low-speed cooling operation: Ecobee dehumidification mode reduces blower CFM during cooling operation improving latent heat removal (subjective humidity feel improvement expected)
  • Longer run times: Right-sized capacity (existing 3.5 ton AC now paired with properly-sized furnace blower rather than oversized furnace blower) enables longer cooling run times per cycle improving dehumidification
  • Baseline humidity target: 45–55% RH during cooling season (down from 55–65% RH baseline with prior single-stage equipment)

Operating Cost Reduction

Anticipated long-term outcome: approximately 15% reduction in Dominion Energy gas consumption reflecting 80% AFUE atmospheric vs 96% AFUE condensing efficiency improvement plus modulation benefits over cycling operation of single-stage prior equipment.

Federal Incentive Coordination

Post-installation incentive coordination: federal IRA 25C tax credit documentation ($600 for qualifying 96% AFUE condensing equipment), and Dominion Energy ThermWise condensing furnace rebate application ($400).

Frequently Asked Questions

What’s the benefit of two-stage versus single-stage furnace?
Two-stage furnace provides substantial comfort benefits over single-stage: (1) reduced temperature swings around setpoint (typical single-stage produces 3–4°F swings, two-stage reduces to 1–2°F swings by running longer at reduced capacity); (2) quieter operation (65% low-fire capacity produces meaningfully lower combustion and blower noise than 100% full-fire operation of single-stage); (3) better humidity control (longer run times at reduced capacity provide more dehumidification during cooling and more consistent humidity distribution during heating); (4) improved efficiency (avoiding oversizing effects of single-stage cycling, better matching to actual heating load which varies throughout heating season); and (5) improved comfort during mild weather (single-stage runs full-blast even when heating load is low, producing overshoot; two-stage low-fire matches mild weather load better). Two-stage is meaningful upgrade over single-stage but not full modulation benefit of variable-speed equipment.
Why two-stage instead of variable-speed modulating furnace?
Equipment tier decision between two-stage 96% AFUE Carrier Performance ($6,400–$8,800) and variable-speed 98% AFUE Carrier Infinity ($8,800–$11,400) considered homeowner priorities and budget: (1) 65% low-fire operation provides much of the comfort benefit of full modulation (temperature swing reduction, longer run times for better humidity control, quieter operation than single-stage) at meaningfully lower cost; (2) 96% AFUE altitude-corrected efficiency essentially equivalent to Infinity 98% AFUE altitude-corrected efficiency in Bluffdale/Riverton climate given altitude correction affects both similarly; (3) ECM variable-speed blower provides continuous fan operation option and modulated blower speed matching stage operation; (4) standard non-communicating thermostat compatibility allows homeowner flexibility in thermostat selection (Nest, Ecobee, or Carrier smart thermostats); and (5) cost savings of approximately $2,400 versus premium tier applied to potential future matched AC replacement or other household priorities. Variable-speed modulation remains available as future upgrade if desired but two-stage typically satisfies most homeowners.
Why furnace replacement without AC replacement at the same time?
2005 matched 3.5 ton Carrier AC continues in acceptable condition with likely 5–10 year remaining service life. Replacement scope analysis: (1) refrigerant system continues to hold refrigerant charge with no leakage observed during recent tune-ups; (2) compressor operation within normal amperage draw range; (3) capacitor and contactor still within acceptable operating range; (4) matched capacity with new furnace blower CFM verified during installation; and (5) 20 year-old equipment approaching end-of-service-life but not yet at critical replacement threshold. Furnace-only replacement scope appropriate given furnace end-of-life while AC continues in service. Homeowner counseled on likely AC replacement timeframe (2027–2030) and encouraged to plan for coordinated replacement when AC condition deteriorates — ideally paired with new Carrier equipment for optimized matching, or heat pump conversion consideration if cold-climate heat pump technology mature at that replacement timing.
Can the existing 2005 AC continue to work with the new 2025 furnace?
Yes, verified during installation. Compatibility considerations: (1) R-410A refrigerant compatible with new furnace blower operation, no refrigerant handling required for furnace replacement scope; (2) existing 2005 evaporator coil (part of furnace configuration but sized for matched 3.5 ton AC) continues in service with new furnace blower; (3) new furnace ECM blower CFM capacity properly matched to 3.5 ton AC (400 CFM/ton = 1,400 CFM design, actual 1,380 CFM measured); (4) new furnace blower cooling-mode CFM verified at 1,380 CFM matching AC capacity; (5) refrigerant system pressures and operation verified after installation completion; and (6) matched AC operation confirmed with proper temperature differential across evaporator (18–22°F range during cooling operation). This coordination allows homeowner to defer AC replacement to when AC condition deteriorates independently rather than replacing simultaneously with furnace.
How does the Ecobee coordinate with the two-stage furnace?
Ecobee SmartThermostat two-stage control coordinates as follows: (1) thermostat call for heat initiates low-fire operation as first response (65% capacity, quieter, longer run time); (2) if home temperature does not reach setpoint after programmed timeout (default 15 minutes), thermostat escalates to high-fire operation (100% capacity for faster recovery); (3) escalation timeout programmable based on homeowner preference (shorter for faster recovery emphasis, longer for quieter operation emphasis); (4) once setpoint achieved, both stages complete cycle and equipment cycles off; (5) ECM blower runs with delayed startup and shutdown coordinated with gas valve operation for optimum efficiency; (6) continuous fan operation available for enhanced humidity control and air distribution; (7) dehumidification mode reduces cooling CFM enabling longer run times for latent heat removal (summer humidity control); (8) room sensor integration averages temperature across primary bedroom and living room providing better whole-home comfort than single-point thermostat reading; and (9) scheduling and geofencing options enable setback and setup coordinated with household patterns. Ecobee Premium provides comprehensive coordination with Carrier Performance two-stage capabilities.

Contact Bluffdale Heating & Air Conditioning

Multi-stage furnace installation with two-stage and variable-speed modulating Carrier equipment tier selection consultation, Manual J load calculation with altitude-adjusted design conditions and right-sizing analysis, Carrier Performance series 59TN6 two-stage 96% AFUE condensing gas furnace installation with ECM variable-speed blower, matched AC compatibility verification and coordinated CFM matching for continuing service on existing equipment, PVC direct-vent installation with side-wall concentric termination and chimney abandonment coordination, Ecobee SmartThermostat Premium installation with two-stage control programming and room sensor integration, combustion analyzer verification at both low-fire and high-fire operation with efficiency measurement, humidity control coordination with cooling season dehumidification mode, federal IRA 25C ($600) and Dominion Energy ThermWise ($400) incentive coordination, and 24/7 emergency response all route through our office at 14659 S 855 W in Bluffdale serving the greater Salt Lake Valley including Riverton Rosecrest.

Contact Us →

Office Hours

  • Emergency Service: 24 hours a day, 7 days a week
  • Office Staff: Monday – Saturday, 9:00 AM – 5:00 PM
  • Closed: Sundays and State/Federal Holidays (emergency line always active)